INSTALLATION INSTRUCTIONS Split System Heat Pump & Air Conditioner WARNING These instructions are intended as an aid to qualified licens
10. Replace cap on service ports. Do not remove the flare caps from the service ports except when necessary for servicing the system. CAUTION
3.9 FACTORY-PREFERRED TIE-DOWN METHOD Step 3: Using L-shaped bracket to locate holes on concrete and drill pilot holes which is 11 at l
12 1/2” bolt 5/16” bolts Fig. 9 COVER AND FAN 3.10 REMOVING THE TOP PANEL AND MOTOR When motor requires changing follow the steps below: Step 1: Go
4.1 GENERAL INFORMATION & GROUNDING Check the electrical supply to be sure that it meets the values specified on the unit nameplate and wi
It will be necessary to evacuate the system to 500 microns or less. If a leak is suspected, leak test with dry nitrogen to locate th
TABLE 2: SUCTION LINE LENGTH/SIZE VS CAPACITY MULTIPLIER(R410A) 15 TABLE 3 :LIQUID LINE SIZE (R-410A) 1 1/2 Ton 2 Ton 2 1/2 Ton 3 Ton 3 1/2 Ton
16 7.3 PROTECTION FUNCTION INTRODUCTION (Heat pump only ) Discharge temperature protection High perssure protection When high pressure > 6
17 8 .2 CHARGING BY WEIGHT For a new installation, evacuation of interconnecting tubing and indoor coil is adeq uate; otherwise, evacuate the e
18 10.0 WIRING DIAGRAM CAUTION These units must be wired and installed in accordance with all National and Local Safety Codes. 9.1 MAINTENANC
19 Fig.14 Outdoor Unit Wiring Diagram for H/P Systems(208/230V 1P 60Hz). OFM ORANGE A2 A1 T1 L1 YELLOW R L1 L2 GND R C Y B D t u o Y C RV C T4 T3
TABLE OF CONTENTS 1.0 SAFETY...3
20 THERMOSTAT C RED GREEN INDOOR UNIT OUTDOOR UNIT Y R G R Y YELLOW BLACK BLACK G C C B R B RED BLUE Fig.15 Control Wiring for H/P Systems.
7909 N.W. 54th Street,Miami, FL 33166 USAPhone: +1 (305) 593-8358Fax: + 1 (305) 593 8212 e-mail: [email protected] www.klimaire.com
1.0 SAFETY This is a safety alert symbol. When you see this symbol on labels or in manuals, be alert to the potential for personal injur
The outdoor units are designed to be connected to a matching indoor coil with sweat connect lines. Sweat connect units are factory charged with refrig
5 FIG.2 DIMENSIONS DIMENSIONAL DATA "H" in. [mm] "W" in. [mm] "L" in. [mm] Liquid in. Vapor in. 18 24-15/16[633] 2
3.0 UNIT INSTALLATION 3.1 LOCATION Before starting the installation, select and check the suitability of the location for both the indoor and outdoor
1. Install the lines with as few bends as possible. Care must be taken not to damage the couplings or kink the tubing. Use clean hard drawn Copp
Insulated Liquid Line Tape Sheet Metal Hanger Correct Incorrect Fig.5 Typical Installation Fig.3 Tubing Hanger Fig.4 Underground Installation All out
CAUTION Dry nitrogen should always be supplied through the tubing while it is being brazed, because the temperature required is high enough to cause o